C H A N G E L O G
Please note: Only use the firmware file in connection with the current software-version of the CCUx!
Device: HmIPW-FAL230-C10 - Homematic IP Wired Floor Heating Actuator 10 channels, 230 V
Company: eQ-3, Maiburger Str. 29, 26789 Leer, Germany
Version 2.4.006 - 2023-08-04
Application: 2.4.006
Bootloader: 1.14.000
BootloaderWired: 1.6.000
Library: 1.64.000
** Bugfix
- In stand-alone mode, the heat pump was not switched off 15 minutes before the last
valves were closed.
- Change from summer to winter time was not working.
- Activation of pump function via select button in FW 2.2.6 not possible
- After a communication error with the wall thermostat has been resolved, the
channel LED may display an incorrect status for up to 15 minutes.
** New Feature
- Added new parameter DEVICE_OPERATION_MODE to enable calculation of improved on times
and post processing planner (for operation with heat pumps).
- Added new parameter HEATING_PWM_CYLCE_TIME.
Version 2.2.006 - 2022-05-30
Application: 2.2.006
Bootloader: 1.14.000
BootloaderWired: 1.6.000
Library: 1.64.000
** Bugfix
- DEC Identify: Time for display illumination was wrong.
The lighting duration of the backlight and the system button by sending the DEC
"Identify" does not correspond to the specification.
- The channel 10 cannot be controlled above 17°C in pairing mode.
After pairing, the device transmits the information to the wall thermostat
whether External Clock is active or inactive. In this case, it is erroneously
transmitted actively, so that the setting of the target temperature on the wall
thermostat is limited.
- Dew point sensor alarm from the MIOB was not forwarded to the MIOB switching
output (dehumidification control).
If dew point alarm was reported by the MIOB, this information was only forwarded to
the wall thermostats but not back to the MIOB to the switching output (dehumidifier
control).
- WTH-2 "%" symbol is not removed when the humidity and dew alarm are cancelled.
- In the case of NormallyOpen, the LED states are not displayed correctly when the
channels are switched on manually on the device.
** Improvement
- The time information telegram does not contain a note about the summer / winter
time change.
So it was possible that a time request to the access point in the period where the
changeover from summer to winter time takes place could lead to a double
changeover.
- Perform valve protection function on all channels
The valve protection function was previously only executed for channels that were
also linked to a wall thermostat. This has changed, the function is now also
executed for channels that do not have a link partner. However, the channels with
a link partner are decisive for the execution.
** New Feature
- Extension of the humidity limit by a pre-limit.
Humidity Monitoring has been extended by a threshold. With the help of this
threshold, a first alarm can be triggered even before the current threshold. The
first alarm activates a dehumidifier in connection with a MIOB, when the second
threshold is triggered, cooling is also stopped, and the corresponding valve is
closed.
Version 2.0.002 - 2019-02-15
First Release.